On grid wind turbine controller | SHJ-3K220 | SHJ-5K220 | ||||
Wind turbine input | ||||||
Power | 3KW | 5KW | ||||
Max. Control power / current | 6KW/20A | 10KW/34A | ||||
Rated voltage of wind turbine (AC) | 220V | 220V | ||||
Input voltage range | AC | 0-330V | 0-330V | |||
DC | 0-450V | 0-450V | ||||
Braking voltage (DC) | Default | 350V±1% | 350V±1% | |||
Set range | 320-350V | 320-350V | ||||
Braking current (DC) | Default | 15A | 25A | |||
Set range | 0-15A | 0-25A | ||||
Braking time | Default | 10-20 min | ||||
Set range | 0-5000 min | |||||
* Generator overspeed control | Default | >300 rpm/min | ||||
Set range | 0-1000 rpm/min | |||||
* Over wind speed control | Default | 14 m/s | ||||
Set range | 0-45 m/s | |||||
Manual control | Manual brake,*remote control brake (with communication function) | |||||
Automatic control function | Dump load control, * yaw, * pitch, * mechanical brake, * hydraulic brake, * electromagnetic brake |
|||||
* PV. Input | ||||||
Rated power (increased) | 3KWp | 3KWp | ||||
Working voltage (DC) | 320V / 400V | 320V / 400V | ||||
DC output parameters | ||||||
Output voltage range (DC) | 0-350V | 0-350V | ||||
Constant voltage (DC) | Default | 310V±1% | 310V±1% | |||
Set range | 300-330V | 300-330V | ||||
Constant current (DC) | Default | 12A | 20A | |||
Set range | 0-12A | 0-20A | ||||
On grid wind turbine inverter | SHJ-3KTL | SHJ-5KTL | ||||
Rated output power (AC) | 3KW | 5KW | ||||
Max. Output power (AC) | 3.3KW | 5.5KW | ||||
Input voltage rang (DC) | 0-450V | 0-450V | ||||
MPPT Voltage range (DC) | 100V-400V | 100V-400V | ||||
Max. Input current (DC) | 11.2A | 18.7A | ||||
Rated current | 10.2A | 17A | ||||
THD Current harmonic | <3%(at rated power) | |||||
Power factor | >0.99 | |||||
Max. efficiency | 98% | |||||
Allowable grid voltage range (AC) | 110V/120V/220V (Single-phase)±20% | |||||
Allowable grid frequency range | 50Hz/60Hz±10% | |||||
Automatic operation conditions | DC input and power grid meet the requirements, the inverter operates automatically | |||||
Restart time after power failure | 2min(Adjustable) | |||||
General parameters | ||||||
Function | Rectification, DC output, output voltage control, output current control, Dump load control, control parameter setting, wind turbine curve setting | |||||
Automatic protection | Control part: Over voltage protection, over current protection, reverse connection protection, lightning arrester Inverter part: Polarity reverse connection protection, short circuit protection, island effect protection,LVRT,overheat protection, overload protection, ground fault protection, etc |
|||||
Display | Touch screen, LCD | |||||
Monitoring content | Wind turbine voltage , current, power, solar panel voltage, current, power, DC output voltage, current, power, inverter output power, * cumulative power generation, * power generation at any time, * rotational speed, * wind speed | |||||
Protection level | IP20(Indoor)IP65 (Outdoors) | |||||
Telematics | RS485/USB/GPRS/WIFI/Ethernet (optional) | |||||
Environment | Operating amb. Temp. & Hum -30-60°C,<90% no condensation | |||||
Noise (1m) | <40dB | |||||
Refrigeration mode | Forced air cooling | |||||
Controller size / weight | 360*230*480mm 17kg | 360*230*480mm 18kg | ||||
Dump load size / weight | 400*400*250mm 12kg | 600*450*380mm 28kg | ||||
Inverter size / weight | 450*275*770mm 39kg | 450*275*770mm 44kg | ||||
On grid wind turbine controller | SHJ-3K380 | SHJ-5K380 | |||
Wind turbine input | |||||
Power | 3KW | 5KW | |||
Max. Control power / current | 6KW/12A | 10KW/20A | |||
Rated voltage of wind turbine (AC) | 380V | 380V | |||
Input voltage range | AC | 0-600V | 0-600V | ||
DC | 0-900V | 0-900V | |||
Braking voltage (DC) | Default | 550V±1% | 550V±1% | ||
Set range | 530-560V | 530-560V | |||
Braking current (DC) | Default | 9A | 15A | ||
Set range | 0-9A | 0-15A | |||
Braking time | Default | 10-20 min | |||
Set range | 0-5000min | ||||
* Generator overspeed control | Default | >300 rpm/min | |||
Set range | 0-1000 rpm/min | ||||
* Over wind speed control | Default | 14 m/s | |||
Set range | 0-45 m/s | ||||
Manual control | Manual brake, *remote control brake (with communication function) | ||||
Automatic control function | Dump load control, * yaw, * pitch, * mechanical brake, * hydraulic brake, * electromagnetic brake |
||||
* PV. Input | |||||
Rated power (increased) | 3KWp | 5KWp | |||
Working voltage (DC) | 550V / 660V | 550V / 660V | |||
DC output parameters | |||||
Output voltage range (DC) | 0-550V | 0-550V | |||
Constant voltage (DC) | 520V±1% | 520V±1% | 520V±1% | ||
510-540V | 510-540V | 510-540V | |||
Constant current (DC) | Default | 7.5A | 12A | ||
Set range | 0-7.5A | 0-12A | |||
On grid wind turbine inverter | SHJ-3KTL | SHJ-5KTL | |||
Rated output power (AC) | 3KW | 5KW | |||
Max. Output power (AC) | 3.3KW | 5.5KW | |||
Input voltage rang (DC) | 0-800V | 0-800V | |||
MPPT Voltage range (DC) | 150V-700V | 150V-700V | |||
Max. Input current (DC) | 6.8A | 11.2A | |||
Rated current | 6.2A | 10.2A | |||
THD Current harmonic | <3%(at rated power) | ||||
Power factor | >0.99 | ||||
Max. efficiency | 98% | ||||
Allowable grid voltage range (AC) | 220V/380V/440V/480V (Three-phase)±20% | ||||
Allowable grid frequency range | 50Hz/60Hz±10% | ||||
Automatic operation conditions | DC input and power grid meet the requirements, and the inverter operates automatically | ||||
Restart time after power failure | 2min(Adjustable) | ||||
General parameters | |||||
Function | Rectification, DC output, output voltage control, output current control, Dump load control, control parameter setting, wind turbine curve setting | ||||
Automatic protection | Control part: Over voltage protection, over current protection, reverse connection protection, lightning arrester Inverter part: Polarity reverse connection protection, short circuit protection, island effect protection,LVRT,overheat protection, overload protection, ground fault protection, etc |
||||
Display | Touch screen, LCD | ||||
Monitoring content | Wind turbine voltage, current, power, solar panel voltage, current, power, DC output voltage, current, power, inverter output power, * cumulative power generation, * power generation at any time, * rotational speed, * wind speed | ||||
Protection level | IP20(Indoor)IP65 (Outdoors) | ||||
Telematics | RS485/USB/GPRS/WIFI/Ethernet (optional) | ||||
Environment | Operating amb. Temp. & Hum -30-60°C,<90% no condensation | ||||
Noise (1m) | <40dB | ||||
Refrigeration mode | Forced air cooling | ||||
Controller size / weight | 360*230*480mm 17kg | 360*230*480mm 18kg | |||
Dump load size / weight | 400*400*250mm 12kg | 600*450*380mm 28kg | |||
Inverter size / weight | 550*225*770mm 49kg | 550*225*770mm 59kg | |||